| MODEL | VS1000C |
| Topology | Standby |
| On-battery Output Waveform | Simulated Sine Wave |
| INPUT | Maximum Capacity | 800VA / 480W |
| Voltage (range) * | 110V +/-25% at line input 120V +20% /-25% at line input 220V +/-25% at line input 230V 240V +15% / -20% at line input |
| Frequency | 50 or 60Hz +/- 10% (auto sensing) |
| OUTPUT | Bypass Capacity | 10A |
| No. of sockets | 2 Battery backup + 1 Surge (US); 2 Battery backup (220V / 230V / 240V) |
| Voltage (on battery) | Rated Voltage |
| Frequency (on battery) | 50 or 60Hz +/- 0.4Hz |
| Transfer Time | 4 ms (typical) |
| PROTECTION | Unit Input | Fuse for overload & short circuit protection |
| Overload Protection | UPS automatic shutdown if overload exceeds 105% of nominal at 20 seconds, 120% at 10 seconds, 130% at 3 seconds. |
| Short Circuit | UPS output cut off immediately |
| BATTERY | Typical Recharge Time (to 90% of full capacity) | 4 Hours |
| Typical Backup | 18-35 mins (a PC with 15" LCD) |
| User Replaceable Battery | 12V / 34W x 1 |
| ENVIRONMENT | Ambient Operation | 3,000 meters max. elevation, 5-90% humidity (No-condensing water), 0-40℃ |
| Audible Noise | < 40dBA (1 meter from surface) |
| WARNING SIGNALS | Communication Port | USB |
| Audible Alarms | Battery back-up, Battery low, Overload, UPS fault |
| PHYSICAL | Weight (Net / Gross) (kg) / (lbs) | 3.6(7.93) / 4.1 (9.03) |
| Dimension (Physical / Packing) (LxWxH) | 7.6 x 2.8 x10.1 / 10.4 x 5.6 x13.3 (in) 194 x 71 x 257 / 263 x 141 x 337 (mm) |
| CONFORMANCE | Approvals | CE, UL/cUL, GOST-R |
| * Models of these nominal voltages are available, however each model is preset to a certain nominal voltage, which is not user-changeable. |