OPTI-UPS International Corporation.
Contact Us
¡½ Product > UPS > Line Interactive UPS Series > Power Series

Line Interactive UPS Series
PS800B
PS1000B
PS1500B
PS2200B
PS3000B
PS1000B-RM
PS1500B-RM
PS2200B-RM
PS3000B-RM
PS500C
PS700C
PS1000C
PS1250C
PS1500C
PS2000C
PS3000C
Power Series -- PS700C
Features
* Pure Sine wave
* Line-interactive design
* Boost and buck AVR
* Overload, AVR, on-line, back up and battery status LEDs display
* Fully digitized microprocessor control
* RS-232 or USB communication port (500VA~700VA models)
* RS-232 and USB communication port (1000VA~3000VA models)
* Lightning and surge protection
* Short circuit and overload protection
* 50/60Hz frequency auto sensing
* Tel / modem / internet spike protection
* Cold start (DC power on)
* Hot swappable battery
* SNMP card slot (PS1000C-PS3000C)

Specifications

Model PS700C
Topology Line-interactive
On-battery Output Waveform Pure Sine Wave
INPUT ¡@
Capacity 700VA/420W
Voltage 100V, 110V, 115V, 120V/ 220V, 230V, 240V*
Frequency 50 or 60Hz +/-10% (auto sensing)
OUTPUT ¡@
Voltage (on battery) Pure sine wave output at nominal +/-5%
Frequency (on battery) 50 or 60Hz +/-0.5%
Voltage Regulation AVR AVR automatically increase output voltage 15% above input voltage if lower than 9% of nominal. AVR decrease output voltage 13% below input voltage if higher than 9% of nominal
PROTECTION AND FILTERING ¡@
Spike Protection 320 Joules, 2ms
Unit Input Fuse or Circuit breaker for overload & short circuit protection
EMI/RFI filter 10dB at 0.15MHz, 50dB at 30MHz
Overload protection UPS automatic shutdown if overload exceeds 110% of nominal at 20 seconds and 125% at 2 seconds.
Transfer Time 2~4 milliseconds (typical)
Short Circuit UPS output cut off immediately or input open protection
BATTERY ¡@
Type Sealed, maintenance free lead-acid
4 hours (to 90% of full capacity)
User Replaceable Batteries 12V / 34W ¡Ñ1
Typical Recharge Time 4 hours (to 90% of full capacity)
Protection Automatic self-test & discharge protection, Replace battery indicator
Back-up Time 10 - 30 minutes (depending on computer load)
ALARM ¡@
Battery Back-Up Slow beeping sound (about 0.25Hz)
Battery Low Rapid beeping sound (about 1.00Hz)
Overload Continue beeping sound
INTERFACE ¡@
RS-232 Interface USB interface Battery test, UPS ON/OFF Schedule,
AC input/output power status display
ENVIRONMENT ¡@
Operation Elevation: 3,500m max, Humidity: 0%-95%(without condensation formation), Temperature: 0-40 deg C
Audible noise <40dBA (1 meter from surface)
Storage condition 15000 meters max. elevation
PHYSICAL ¡@
Weight Kg(Net/Gross) 15.6 / 17.4 (lbs)
6.7 / 7.9
(kg)
Dimension(Physical/Packing)
(L¡ÑW¡ÑH)
12.6 ¡Ñ 3.8 ¡Ñ 5.3 / 16 ¡Ñ 7.6 ¡Ñ 10.2 (in)
320 ¡Ñ 97 ¡Ñ 135 / 406 ¡Ñ 192 ¡Ñ 258
(mm)
¡@
Copyright ® 2008 OPTI-UPS International Corporation all rights reserved