Durable Series -- DS60KC33
Energy Saving :
With such high efficiency, you will save on energy consumption. This ensures lower operation costs and faster returns on your investments.

Topology:
Double Conversion
Rating:
10KVA to 120KVA
Voltage:
208V/120V,380V/220V

Applications:
* Industrial
* Medical
* ISP/ASP/POP
* Servers
* Data Centers
* Telecommunications

Features
* Highest performance and reliability using DSP (Digital Signal Processor)
* SPWM (Sinewave Pulse Width Modulation) and IGBT to handle even the most difficult industrial applications
* User-friendly interface and multi-functional display allowing access to a variety of parameters

Specifications

Model

DS

60KC33

Capacity

60KVA

Rating Power

48KW

Power factor

0.8

AC input

Phase

3 Phase 3 wire / 3 Phase 4 wire and ground

Voltage

380V/220V or 208V/120V ±20 %

Frequency

Auto-sensing, 50Hz/60Hz ±5 Hz

Regulation style

3 phase 6 pulses or 12 pulses (option)

DC voltage

DC410V

Efficiency of rectifier

>97%

Efficiency of Inverter

>88%

Total Efficiency

>85%

Output

Phase

3 phase 4 wire and ground

Voltage range

380V/220V or 208V/120V

Voltage regulation

±1%

Transient state

Return to 90% with 4 cycle

Overload capacity

Bypass after 30 min while overload >100% <125%

Bypass after 30 sec while overload =125% <150%

Bypass after 30 cycles while overload exceed 150%

Way of Inverter

Sine wave modulated from 20KHz pulse by DSP control

Frequency

50Hz/60Hz

Frequency regulation

±0.1%

Range of phase lock

±5 Hz

Range of lock released

>±5 Hz

Range of lock back

±3 Hz

Wave

Sine wave

Load crest factor

3:1

Total harmonic distortion

Less 3% linear load

Static Switch

Transfer way

When inverter and utility are synchronized at same phase and voltage, bypass

Transfer time

Bypass to inverter 0mS

Normal state, inverter to bypass 0mS

Efficiency

> 99%

Charger

Voltage

DC410V

Current

Current can be adjusted at 1A, 2A, 3A, 5A, 10A, 15A, 20A, 30A automatically

Charging period

Return to 90% from 100% exhausted battery within 8 hours (depending on type of batteries)

Utility

Battery type

Bank with 12V X 30 pcs

Backup time

Depending on type of batteries

Noise

Less than 60dBA from the surface of 1m away

Environment

Operation Temperature

0~40

Storage Temperature

-25~55

Ambient operation

3,500 meters max. elevation, 0-95% humidity non-condensing

Model

DS

60KC33

PHYSICAL

380V /220V

Dimensions (Physical / Packing)
(L×W×H)

31.5×29.5×66.9 / 36.8×34.8×75 (inches)
800×750×1700 / 935×885×1905(mm)

Weight (Net / Gross) (lbs)

1389.9 / 1610.1 (lbs)
631 / 731 (kg)

208V /120V

Dimensions (Physical / Packing)
(L×W×H)

31.5×29.5×66.9 /36.8× 34.8×75(inches)
800×750×1700 / 935×885×1905(mm)

Weight (Net / Gross)

1874.4 / 2094.7 (lbs)
851 / 951 (kg)

 
Copyright ® 2008 OPTI-UPS International Corporation all rights reserved